Design and contract administration for hybrid pump station

This station was designed as a cross between a typical fire pump installation and a municipal pump station.

Each of the fire pumps provide 126 L/s (2000 usgpm) and are controlled by rated fire pump controllers. A jockey pump is provided to maintain system pressure. Each pump has a listed inlet pressure sustaining valve to maintain upstream pressure and prevent the collapse of the HDPE supply main. A listed pressure relief valve relieves back to the pump station suction header.